General description

Article number 100-8018
IEC 60068-2-27
Sine vibration (based on IEC 60068-2-6) 5 ~ 25Hz: ±1.6mm 25 ~ 300Hz: 4g Sweep rate: 1 octave/min., 20 cycles Random vibration (based on IEC 60068-2-64) 10 ~ 40Hz: 0.0125g²/Hz 40 ~ 100Hz: 0.0125 → 0.002g²/Hz 100 ~ 500Hz: 0.002 g²/Hz 500 ~ 2000Hz: 0.002 → 1.3 x 10-4g²/Hz Test time: 1hrs for each test
EN 61000-6-4/A11: 2011
EN 61000-6-2 : 2005
Variable
CE, UL, FCC, RoHS, China RoHS, Reach
Supply voltage: 24VDC nominal Supply voltage range: 15 ~ 32VDC Protection: output current limit (1.5A) Reverse polarity protection
110mA @ 24VDC
1.5A @ 5Vdc
Supply voltage: 24VDC typical (Max. 32VDC) * Field power range depends on installed IO module(s) . Refer to IO module’s specification.
VDC 10 A max
167g
54x99x70mm

Communication

CE, UL, FCC, RoHS, China RoHS, Reach
2400 ~ 115 200bps (RTU), 10 / 100Mbps (TCP)
IP-address (adjustable via DIP-switch)
9pin D-sub (RTU), RJ45 (TCP)
First module

Environmental

35mm DIN rail
60 ~ 70℃: power dissipation is limited to 0.8A -40 ~ 60℃: 1.5A full load is allowed
-40~85℃
-20~60℃
5 ~ 90% non-condensing

Digital input module specifications

Indicators 6 LEDs 1 green / red, module status (MOD) 1 green / red, network status (NET) 1 green / red, PLC Run/Stop status (RUN) 1 green / red, expansion I/O module status (IOS) 1 green, system power status 1 green, field power Status

Analog input module specifications

Indicators 6 LEDs 1 green / red, module status (MOD) 1 green / red, network status (NET) 1 green / red, PLC Run/Stop status (RUN) 1 green / red, expansion I/O module status (IOS) 1 green, system power status 1 green, field power Status

Analog output module specifications

Indicators 6 LEDs 1 green / red, module status (MOD) 1 green / red, network status (NET) 1 green / red, PLC Run/Stop status (RUN) 1 green / red, expansion I/O module status (IOS) 1 green, system power status 1 green, field power Status